Engineered as one thermal and power system.
The chassis is built around the cooling loop, the PCIe slot layout follows the loop’s physical envelope, and power distribution is platform-level. It is not a board dropped into a case; it is a platform designed as a single engineering problem.
A barebone platform: LM TEK supplies the chassis, the integrated cooling loop, and platform-level power. You specify the board, CPUs, GPUs, memory, and storage.
01 · Subsystem
Density
Liquid cooling collapses each GPU’s thermal solution into a single-slot water block. That, not a bigger box, is how eight full-height PCIe Gen 5 cards fit in a 4U envelope.
The chassis is engineered around standard EATX server motherboards rather than a proprietary board. PCIe slot positions and clearance accommodate the cooling loop without needing custom riser cards. Mounting hardware is rack-standard. The platform takes ordinary enterprise components and arranges them at extraordinary density.
| Rated | Value |
|---|---|
| GPU slots | Up to 8 × full-height PCIe Gen 5 |
| Form factor | 4U · 19-inch rack chassis |
02 · Subsystem
Upgrade in place
The chassis, loop, and power are sized for the full eight-GPU end state on day one. A two-GPU entry build grows inside the same chassis and on the same loop, in the same four rack units.
A supported accelerator comes from the published compatibility list, with its water block. Anything outside the list is a bespoke project with LM TEK engineering.
| Rated | Value |
|---|---|
| Entry build | Two GPUs |
| End state | Eight full-height PCIe Gen 5 GPUs |
| CPU | Single-socket to dual-socket is a board choice |
03 · Subsystem
The loop
The chassis is built around the closed cooling loop, and the PCIe slot layout follows the loop’s physical envelope rather than a board form factor. Pump, manifold, GPU and CPU water blocks, radiator, and reservoir all live inside the chassis, with the radiator on the front intake so airflow paths are engineered alongside the loop.
Maximum working pressure for the assembled loop is 0.6 bar, set by the radiators. There is no external CDU or facility plumbing.
| Rated | Value |
|---|---|
| Loop type | Closed integrated loop, fully in-chassis |
| Radiator placement | Monolith triple-width pass-through radiator · front intake; airflow paths engineered alongside the loop |
| Radiator core | 130 mm thick core · 120 × 360 mm standard cooling surface · fits 3 × 120 mm standard fans per side |
| Fans | 6 × industrial-grade fans |
04 · Subsystem
The blocks
The loop uses the materials discipline, pressure envelope, and manifold geometry of the LM TEK liquid-cooling catalogue, transferred to enterprise rack scale. Cooling designed by the EK engineering team, twenty-five years deep in high-performance liquid cooling.
Block availability is part of the published compatibility list.
| Rated | Value |
|---|---|
| Coolant materials stack | Nickel-plated copper · stainless steel · POM Acetal · EPDM · brass · EK-CryoFuel |
| GPU and CPU water blocks | Matched to the chosen GPUs and CPUs |
05 · Subsystem
Platform power
80 PLUS Titanium PSUs, 5 × 2 kW with redundancy, and a platform-level PDU size the GPU power budget at the chassis, not the board.
The customer’s motherboard chooses CPU and memory; the platform chooses how power reaches the GPUs.
| Rated | Value |
|---|---|
| Power supply | 5 × 2 kW with redundancy · CRPS · 80 PLUS Titanium |
| Power distribution | Platform-level PDU · independent of motherboard VRM |
| PSU redundancy | 5 × 2 kW with redundancy · implemented by the platform PDU |
06 · Subsystem
Control and protection
The server preset holds the coolant at 50°C at the hottest point in the loop, which favours sustained performance. For the controller revision and monitoring integration in a given deployment, talk to LM TEK engineering.
Protective functions are integral to safe operation: the system shuts down at 60°C coolant temperature, performs a hard shutdown if either pump fails, and boots only when at least one pump reports function. Do not bypass or disable these protections.
An audible alarm signals fan failure. Investigate and resolve the alarm before continued operation.
| Reported controller behaviour | Value |
|---|---|
| Coolant temperature target | Server preset universal at 50°C at the hottest point in the loop |
| Coolant temperature | System shutdown at 60°C coolant temperature |
| Pump failure | Hard shutdown on failure of either pump |
| Boot interlock | System boots only when at least one pump reports function |
| Fan failure | Audible alarm on any fan failure |
07 · Subsystem
Service and access
Dry-break quick disconnects support block replacement with the server racked. Integrated IN/OUT service ports provide access for an automated drain, flush and fill cycle without opening the loop. Front fill access and the reservoir window provide access and visibility.
| Rated | Value |
|---|---|
| Serviceability | Dry-break front quick-disconnect couplings · built-in coolant level indicator (reservoir window) |
| Storage bay | Single mounted drive bay for 5 × 2.5-inch drives · in chassis airflow path · positioned for straightforward access during service |
The platform in detail.
-
Specifications
The full datasheet, cooling loop specifications, reference configurations and dimensions.
Read the full datasheet → -
Validation
The rated envelope beside measured runs, each with its conditions and source.
See the measured runs → -
Resources
Published documents, drawings and video, and what LM TEK supplies on request.
Browse the documents →
A published compatibility list; bespoke projects with engineering.
The platform ships with a published compatibility list: supported board formats and sockets, GPUs with available water blocks, and the operating limits. A configuration built from it is quotable as is. Anything outside it, such as another GPU or a custom cooling solution, is a bespoke project with LM TEK engineering.
Modification projects →